Determination of the most effective switching signal and position of braking resistor in DFIG wind turbine under transient conditions

  • Kenneth Okedu Department of Electrical and Electronic Engineering Kitami Institute of Technology, Hokkaiddo, Japan

Abstract

A quick post fault recovery of wind generator system could be achieved with the help of a series dynamic braking resistor (SDBR). This paper investigates the dynamics, size, optimal location of a series dynamic braking resistor in the Doubly Fed Induction Generator (DFIG) structure based on different switching strategy of the braking resistor. Three signals were investigated in switching the SDBR during transient conditions of the DFIG wind generator; the DC-link voltage, rotor current and grid voltage respectively. Also, three locations were considered in connecting the SDBR in the DFIG system; the stator, rotor and grid side converter respectively. Furthermore, the optimum size and best insertion time of the SDBR were investigated based on the most effective performance of the SDBR scheme considering its switching signal and position in the DFIG system. Simulations were run in Power System Computer Aided Design and Electromagnetic Transient Including DC (PSCAD/EMTDC). The results show that when the SDBR is connected to the DFIG, improved performance was achieved, however, the stator based SDBR topology in conjunction with a grid voltage actuating signal, fast insertion time and short duration of operation, quickly recovered the DFIG wind generator variables during transient conditions.
Published
2023-10-08
How to Cite
OKEDU, Kenneth. Determination of the most effective switching signal and position of braking resistor in DFIG wind turbine under transient conditions. Journal of Power Technologies, [S.l.], v. 103, n. 3, p. 146-158, oct. 2023. ISSN 2083-4195. Available at: <https://papers.itc.pw.edu.pl/index.php/JPT/article/view/1358>. Date accessed: 02 may 2024.
Section
Renewable and Sustainable Energy

Keywords

Renewable energy; DFIG; Power converters; Grid fault; Series dynamic braking resistor

Most read articles by the same author(s)

Obs.: This plugin requires at least one statistics/report plugin to be enabled. If your statistics plugins provide more than one metric then please also select a main metric on the admin's site settings page and/or on the journal manager's settings pages.